Customization: | Available |
---|---|
Usage: | Fire Lights |
Emergency Time: | 3-4h |
Still deciding? Get samples of US$ 15/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Parameters
Operation | Non-Maintained |
Input Voltage | 110V-127V 50/60HZ,220V-240V 50/60HZ |
Charging Current | 40mA(Nominal) |
Lamp Used | 3W SMD White LED |
Battery | Ni-cd Battery 3.6V 1.0AH |
Indication |
Green LED Indicates Charging |
IP Rate | IP20 |
Installation | Ceiling Recessed |
Weight | 0.5KG |
Product Size | 350mmx110mmx38mm Tolerance ±0.03mm |
Features
Operating Temperature | -10°C to 55°C |
Construction | Electro-galvanized Steel Casing, PC Plate |
Duration Time | >3HRS |
Indicator status without test button operation
Indicator |
Performance |
Means Status |
Red |
Lit |
Charging |
Green |
Lit |
Fully charged |
Slow blink(1Hz) |
Manual check mode |
|
blink(3Hz) |
Automatic monthly self-check mode |
|
Quick blink(5Hz) |
Automatic annual self-check mode |
|
Yellow |
Lit |
Battery aging, or too short emergency time |
Slow blink(1Hz) |
Battery is in short circuit or open circuit |
|
blink(3Hz) |
Wrong connection with lamps or not matchable lamps |
|
Off |
|
Emergency or stop working condition |
Test Button Operation and Indicator Status
Pressed time |
Indicator status |
Check mode |
<1s |
No reaction |
None. To avoid mistakenly operating |
1~3s |
Slow blink (1Hz) in green |
check mode and discharge for 5 seconds |
3~5s |
blink(3Hz) in green |
monthly self-check mode and discharge for 2 mins |
5~7s |
Quick blink(5Hz) in green |
annual self-check mode and discharge for 1 hour |
>7s |
|
Stop discharging to recharge again |
Function